a) Cabinet Defrost: Power Switch "ON," Rail Cooling Switch "OFF"
CLLV continues, CabFM, Comp, ConFM, and PH de-energize. DH energizes and
warms DTh to 49°F (9.4°C) (or the 100-minute defrost termination timer expires
or DTst warms to 120°F±5°F (49°C±3°C)). When DTh reaches 49°F (9.4°C),
DH de-energizes, CLLV continues and a 5 minute Comp delay timer starts. When the
5-minute Comp delay timer expires, CabFM and PH energize for 10 seconds. Comp
and ConFM then energize and a 5-minute CabFM and PH delay timer starts. After the
5-minute CabFM and PH delay timer expires, CabFM and PH energize.
b) Cabinet Defrost: Power Switch "ON," Rail Cooling Switch "NORMAL" or "LOW"
(1) Cabinet cool down achieved, rail still cooling
Comp, CondFM, RailFM, and RLLV continue. CabFM and PH de-energize, and
CLLV remains de-energized. DH energizes and warms DTh to 49°F (9.4°C) (or
the 100-minute defrost termination timer expires or the DTst warms to 120°F±5°F
(49°C±3°C)). When DTh reaches 49°F (9.4°C), DH de-energizes, Comp, ConFM,
RailFM, and RLLV continue. CabFM and PH energize for 10 seconds. CLLV then
energizes and a 5-minute CabFM and PH delay timer starts. After the 5-minute
CabFM and PH delay timer expires, CabFM and PH energize.
(2) Cabinet still cooling, rail cool down achieved
RailFMcontinues(RailFMcontinueswhenrailswitchisinthe"NORMAL"
positionandperF9settingwheninthe"LOW"position),RLLVandDHenergize,
CabFM, Comp, ConFM, and PH de-energize. CLLV de-energizes for 2 seconds,
then energizes again. DH warms DTh to 49°F (9.4°C) (or the 100-minute
defrost termination timer expires or the DTst warms to 120°F±5°F (49°C±3°C)).
When DTh reaches 49°F (9.4°C), DH de-energizes, RailFM continues, RLLV
de-energizes, CLLV energizes, and a 5-minute Comp delay timer starts. When the
5-minute Comp delay timer expires, CLLV and RailFM continue. CabFM and PH
energize for 10 seconds. Comp and ConFM then energize and a 5-minute CabFM
and PH delay timer starts. After the 5-minute CabFM and PH delay timer expires,
CabFM and PH energize.
6. Rail Defrost
For rail defrost (manual defrost), remove product from the rail area and store in a
properlyrefrigeratedarea,thenmovetherailcoolingswitchtothe"OFF"position.
Legend: CabFM–cabinet fan motor; CB–control board; Comp–compressor;
ConFM–condenser fan motor; CLLV–cabinet liquid line valve; CTh–cabinet
thermistor; DH–defrost heater; DT–defrost timer; DTh–defrost thermistor;
DTst–defrost thermostat; PH–perimeter heater; RailFM–rail fan motor; RLLV–rail
liquid line valve; RTh–rail thermistor