2. Low Temperature Alarm (E2)
If the cabinet or rail temperature drops below the setpoint temperature by 9°F (5°C) or
moreformorethanyhours,"E2"isdisplayed.Thedefaultvalueofyis"1"(1hour).The
valueofycanbechangedunder"F4"ontheservicemenu.(0=Nodelay;1=1hour)
Note:
•Thelowtemperaturealarmtimerstartsoncethecabinettemperaturedrops9°F
(5°C) below the setpoint temperature.
•Thelowtemperaturealarmfeatureoperatesevenduringdefrost.
Reset Options
The alarm will automatically reset once the area temperature reaches the upper setpoint
temperature differential.
Possible Causes (forfurtherdetailssee"III.B.ServiceChart")
•Ambienttemperatureislow.
•Troublewiththecabinetthermistor(black).
•Liquidlinevalveopen.
•Evaporatorfansnotoperating.
E2 Alarm
Timer Reset
E2 Alarm Reset
Power On
E2 Alarm Temperature
9°F (5°C) below setpoint temp.
Lower Setpoint Temperature
Differential -3.6°F (2°C)
E2 Alarm
Timer over
1 hour
Temperature Display
E2
Blinking
E2 Alarm Timer
under 1 hour
Setpoint Temperature and
Upper Setpoint Differential 0°F (0°C)
E2 Alarm