III. Service Diagnosis
WARNING
1. This unit should be disassembled or repaired only by a qualied service
technician to reduce the risk of injury, electric shock, or re.
2. Do not make any alterations to the unit. This could cause water leak, electric
shock, or re.
3. To help reduce the risk of electric shock, do not touch the attachment plug or
switches with damp hands.
4. In case of insufficient refrigeration performance, move the stored food
product into another unit to prevent its deterioration.
A. Alarm Signals
In the event of operation outside of normal parameters, the control board identies the
issue with an alarm signal. The alarm signal and cabinet temperature are displayed in
1‑secondintervals.Forfurtherserviceinformation,see"III.B.ServiceChart."Ifmultiple
alarms occur simultaneously, only the alarm with the higher priority is displayed.
Alarm
Signal
Priority Problem Reset, Corrections, and Adjustments
E1 8
High Temperature Alarm (cabinet only)
Cabinet temperature has exceeded the
setpoint temperature by 18°F (10°C) for
more than x hours. The default value of
xis"2".
When the temperature returns to the setpoint
range, alarm resets.
Close doors/drawers and clean the condenser and
air lter. Check for refrigerant leaks. Check cabinet
thermistor.
Thevalueofxcanbechangedunder"F3"onthe
Service Menu.
(0=No delay; 1=1 hour; 2=2 hours; 3=3 hours)
E2 9
Low Temperature Alarm (cabinet only)
Cabinet temperature has remained
below the setpoint by 9°F (5°C) for more
than y hours. The default value of y is
"1".
When the temperature returns to the setpoint
range, alarm resets.
Ambient temperature too low. Check thermistor,
liquid line valve sticking, fans not operating.
Thevalueofycanbechangedunder"F4"onthe
Service Menu.
(0=No delay; 1=hour)
E3 7
Defrost Alarm (cabinet only)
Cabinet defrost has taken longer than
1 hour. The control board has terminated
defrost.
Turn the power off, then back on.
Check defrost heater, defrost thermistor.
Notethat"E3"mayalternatewith"dF"insteadof
the temperature.