4. High Condenser Temperature Alarm (clogged lter) (E7)
The unit is equipped with a condenser air lter to protect the condenser from dirt, grease,
etc. The condenser air lter promotes clean condenser surfaces and efficient operation
and should be checked twice monthly and cleaned when necessary. The unit is also
equipped with a condenser thermistor to determine if the condenser or condenser air
lter is excessively dirty. If the condenser thermistor detects a temperature that exceeds
thepresettemperaturevalue(136.4°F(58°C))forover2minutes,"E7"willbedisplayed.
CAUTION
Failure to take action when this alarm activates could result in damage to the
compressor.
Reset Options
After cleaning the lter, the alarm will automatically reset once the temperature at the
condenser outlet drops below 136.4°F (58°C).
Possible Causes (forfurtherdetailssee"III.B.ServiceChart")
•Thecondenserorcondenserairlterisdirty.
•Thecondenserfanmotorisnotfunctioning.
Note: If the power is turned off and then back on while the alarm signal is displayed,
the alarm may be reset even if the condenser or condenser air lter has not
been cleaned. However, the alarm will repeat once the compressor discharge
temperature reaches 136.4°F (58°C).
E7 Alarm
Reset
2 min
High
E7 Alarm Temp.
136.4°F (58°C)
Temperature Display
E7 Alternating
with Temperature
E7 Alarm Timer Start
Low
E7 Alarm