B. Sequence of Operation
The steps in the sequence are as outlined below.
1. Startup
Whenthepowerswitchisinthe"ON"position,thecabinettemperatureisdisplayed
andcabinetcoolingbegins.Whenthepowerswitchisinthe"ON"positionandtherail
coolingswitchismovedtothe"NORMAL"or"LOW"position,therailtemperatureis
displayedandrailcoolingbegins.The"NORMAL"railswitchpositionisdesignedforuse
whentherailcoverisopen.The"LOW"railswitchpositionisdesignedforusewhenthe
railcoverisclosed.Forfurtherdetails,see"II.D.4.a)SwitchSettings."
a) Power Switch "ON," Rail Cooling Switch "OFF"
Cabinet temperature at or above setpoint: CabFM, CLLV, and PH energize. The
2 minute Comp delay timer and 6 hour DT start.
b) Power Switch "ON," Rail Cooling Switch "NORMAL" or "LOW"
Cabinet temperature and rail temperature at or above setpoint: CabFM, CLLV, PH,
RailFM, and RLLV energize. The 2 minute Comp delay timer and 6 hour DT start.
2. Cool Down
a) Power Switch "ON," Rail Cooling Switch "OFF"
CabFM, CLLV, and PH continue. The 2 minute Comp delay timer expires and Comp
and ConFM energize.
b) Power Switch "ON," Rail Cooling Switch "NORMAL" or "LOW"
CabFM, CLLV, PH, RailFM, and RLLV continue. The 2 minute Comp delay timer
expires and Comp and ConFM energize.
3. Cool Down Achieved
TopreventComphardstarts,CLLV(railcoolingswitch"OFF")orRLLV(railcooling
switch"NORMAL"or"LOW")remainsenergizedwhenCompisoff.
a) Power Switch "ON," Rail Cooling Switch "OFF"
CTh reaches 3.6°F (2°C) below setpoint. CabFM and PH continue, Comp and ConFM
de-energize. CLLV de-energizes for 2 seconds (CLLV then remains energized during
Comp off time).
b) Power Switch "ON," Rail Cooling Switch "NORMAL" or "LOW"
CTh, RTh, or both have reached 3.6°F (2°C) below setpoint.
(1) Cabinet still cooling, RTh reaches 3.6°F (2°C) below setpoint
CabFM, Comp, CondFM, CLLV, and PH continue. RailFM continues when rail
coolingswitchisinthe"NORMAL"positionandperF9settingwheninthe"LOW"
position.Fordetails,see"II.D.4.a)SwitchSettings."RLLVde‑energizes.
(2) CTh reaches 3.6°F (2°C) below setpoint, rail still cooling
CabFM, Comp, CondFM, PH, RailFM, and RLLV continue. CLLV de-energizes.