C. Sequence of Operation Charts
1. Cabinet Cooling
Legend:
CabFM-cabinet fan motor
Comp-compressor
ConFM-condenser fan motor
CLLV-cabinet liquid line valve
CTh-cabinet thermistor
DH-defrost heater
DT-defrost timer
DTh-defrost thermistor
DTst-defrost thermostat
PH-perimeter heater
CabFM energized
CLLV energized
PH energized
Comp de-energized
ConFM de-energized
4. Cabinet Defrost
1. Startup 2. Cool Down 3. Cool Down Achieved
CabFM energized
CLLV energized
Comp energized
ConFM energized
PH energized
CTh in control
DTh reaches 49°F (9.4°C) or
100-minute defrost termination timer expires or
DTst temperature reaches 120°F±5°F (49°C±3°C)
CabFM energized
CLLV energized
PH energized
CTh warms to
setpoint
•2‑minute
Comp delay
timer starts
•6‑hourDT
starts
5. Cabinet Cool Down Defrost Recovery
(defrost terminated)
CabFM energized
CLLV energized
Comp energized
ConFM energized
PH energized
Stage 1:
5-minute Comp
delay timer
DTh in control
To 5 below
From 5 below
To 2 above
From 4
above
•6hourDTexpires,then
resets
•100‑minutedefrost
termination timer starts
CabFM and PH
energize for 10 sec.
CLLV energized
Comp energized
ConFM energized
Stage 2:
5-minute CabFM and
PH delay timer
Power Switch "ON," Rail Cooling Switch "OFF"
CLLV energized
DH energized
CabFM de-energized
Comp de-energized
ConFM de-energized
PH de-energized
CLLV energized
DH de-energized
CabFM de-energized
Comp de-energized
ConFM de-energized
PH de-energized
CTh reaches
3.6°F (2°C)
or more
below setpoint
2-minute Comp
delay timer starts
Cycle Steps
Initial startup
begins here