(3) Both CTh and RTh reach 3.6°F (2°C) below setpoint
CabFM and PH continue. RailFM continues when rail cooling switch is in the
"NORMAL"positionandperF9settingwheninthe"LOW"position.Fordetails,
see"II.D.4.a)SwitchSettings."Comp,ConFM,andCLLVde‑energize.RLLV
de-energizes for 2 seconds. RLLV energizes, then remains energized during
Comp off time.
4. Cool Down Restart
a) Power Switch "ON," Rail Cooling Switch "OFF"
CTh warms to setpoint, the CabFM, CLLV, and PH continue. 2 minute Comp delay
timer starts. After the 2 minute delay timer expires, Comp and ConFM energize.
Cycle continues until power is turned off, the 6 hour DT expires and CB initiates
acabinetdefrost,orthe"MANUALDEFROST"buttonispressedfor5seconds
(evaporator temperature must be below 49°F (9.4°C)).
b) Power Switch "ON," Rail Cooling Switch "NORMAL" or "LOW"
CTh, RTh, or both have warmed to setpoint.
(1) CTh at or above setpoint, RTh warms to setpoint
CabFM, Comp, ConFM, CLLV, PH, continue. RailFM continues when rail switch is
inthe"NORMAL"positionandresumescontinuousoperationwheninthe"LOW"
position. RLLV energizes.
(2) CTh warms to setpoint, RTh at or above setpoint
CabFM, Comp, ConFM, PH, RailFM, and RLLV continue. CLLV energizes.
(3) CTh or RTh warms to setpoint
CabFM,PH,RailFM(RailFMcontinueswhenrailswitchisinthe"NORMAL"
positionandresumescontinuousoperationwheninthe"LOW"position),and
RLLV continue. The 2 minute Comp delay timer starts. If CTh has warmed to
setpoint and RTh has not, CLLV energizes and RLLV de-energizes. If RTh
has warmed to setpoint and CTh has not, RLLV continues and CLLV remains
de-energized. After the 2 minute Comp delay timer expires, Comp and ConFM
energize.
5. Cabinet Defrost
The rst cabinet defrost occurs 6 hours after the unit is turned on. Cabinet defrost is
initiatedwhenthe6hourDTexpiresorthe"MANUALDEFROST"buttonispressed
for 5 seconds. Cabinet defrost termination occurs when the evaporator temperature
reaches 49°F (9.4°C). Note that the defrost is a heated defrost, and therefore will have a
tendency to raise the cabinet temperature. Cabinet temperature is not displayed during
defrost;"dF"isdisplayedinitsplace.Afterdefrost,thereisa5minutedelaybeforethe
compressor will start.
Note:TopreventComphardstarts,CLLV(railcoolingswitch"OFF")orRLLV(rail
coolingswitch"NORMAL"or"LOW")remainsenergizedwhenCompisoff.