(2) Connection to a Closed Loop System
Condenser Water
Supply Inlet
Minimum Condenser
Water Supply Line Size
Condenser
Return Outlet
Minimum Condenser
Return Line Size
1/2" Female Pipe
Thread (FPT)
1/4" Nominal ID Copper
Water Tubing or Equivalent
3/8" Female Pipe
Thread (FPT)
1/4" Nominal ID Copper
Water Tubing or Equivalent
• Shut-off valves and drain valves must be installed at both the condenser water supply inlet
and condenser return outlet.
• Minimum water ow to the condenser is 4 GPM.
The pressure differential between the condenser water supply inlet and condenser return
outlet must be no less than 10 PSIG.
When using a glycol blend, the solution mixture should be less than 30% glycol.
• In order to maintain the proper high side pressure, the condenser water supply inlet
temperature should not drop below 45°F (7°C) and the condenser return outlet
temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker
installation is complete, conrm the condenser return outlet temperature 5 minutes after a
freeze cycle starts. If the condenser return outlet temperature is not in the proper range,
use a at blade screwdriver to rotate the adjustment screw on the water-regulating valve
until the temperature is in the proper range (rotate counterclockwise to raise temperature
or clockwise to lower temperature).
Fig. 6
Water-Cooled Models
Connection to a Closed Loop System
Model Shown:
KML-451MWH
Icemaker
Icemaker Water
Supply Inlet
1/2" FPT
Bin Drain Outlet
3/4" FPT
2-inch (5-cm) air gap
Floor
Drain
Icemaker
Drain Outlet
3/4" FPT
Vent Tube
Vent Tube
Condenser Water
Supply Inlet
1/2" FPT
Condenser
Return Outlet
3/8" FPT
Shut-Off Valve
Minimum 1/4" Nominal ID Copper
Water Tubing or Equivalent
Drain Valve
Ice
Storage
Bin
Minimum 3/4" Nominal ID
Hard Pipe or Equivalent
Separate piping to approved
drain. Leave a 2-inch (5-cm)
vertical air gap between the
end of each pipe and the
drain.
Be sure there is sufficient
extra water supply line and
drain line for the appliance
to be pulled out for service.