HOSHIZAKIMODULAR CRESCENT CUBERSERVICE MANUALKML “F” SERIESKML “H” SERIESMODELSNO.:ISSUED:REVISED:AUG. 18, 1999JAN. 13, 200473085
105. KML-350MAH
10011. REMOVAL AND REPLACEMENT OF THERMISTORCAUTION1. Fragile, handle very carefully.2. Always use a recommended sealant (High Thermal Conductive Type
10110) Secure the insulation using the Plastic Cable Ties.11) Connect the Thermistor leads through the bushing of the Control Box to the K3Connector o
10213. REMOVAL AND REPLACEMENT OF WATER VALVE1) Turn off the power supply.2) Close the Water Supply Line Shut-off Valve.3) Remove the Front Panel.4) R
10315. REMOVAL AND REPLACEMENT OF SPRAY TUBES1) Turn off the power supply.2) Remove the Front Panel and the Insulation Panel.3) Remove the Rubber Hose
104VI. MAINTENANCE AND CLEANING INSTRUCTIONSIMPORTANTEnsure all components, fasteners and thumbscrews are securely in place afterany maintenance or c
105[2] Remove the water from the potable water supply line:1) Turn off the power supply and remove the Front Panel.2) Move the Control Switch, on the
106MODEL WATER "SCALE AWAY" WATER SANITIZERgal. fl. oz. gal. fl. oz.KML-250 2 10.5 2 1KML-350 2 10.5 2 1KML-450 2 10.5 2 1KML-600 2.5 13.5 2
1075) Place the Control Switch in the “SERVICE” position. Then place the Service Switch in the “DRAIN” position.6) Replace the Front Panel and tur
1083. SANITIZING PROCEDURE - Following Cleaning Procedure1) Dilute a 5.25% Sodium Hypochlorite solution (chlorine bleach) with water (Add 1.0 fl.
1094. MAINTENANCEIMPORTANTThis icemaker must be maintained individually, referring to the instructionmanual and labels provided with the icemaker.1) S
116. KML-350MWH (Beginning serial #L00001J, ending Serial #M20060C)
127. KML-350MWH (Beginning serial #M30061E)
138. KML-450MAF
149. KML-450MWF
1510. KML-450MAH
1611. KML-450MWH (Beginning Serial #L00001D, ending Serial #M10530B)
1712. KML-450MWH (Beginning Serial #M20531D)
1813. KML-600MAF
1914. KML-600MWF
2IMPORTANTOnly qualified service technicians should attempt to service or maintain this icemaker.No service or maintenance should be undertaken until
2015. KML-600MRF
2116. KML-600MAH
2217. KML-600MWH (Beginning Serial #L00001D, ending Serial #M10115C)
2318. KML-600MWH (Beginning Serial # M10121E)
2419. KML-600MRH
2520. CONDENSER UNITURC-7FUnit: mm. (inches)
26SPECIFICATIONSURC-7F
27II. GENERAL INFORMATION1. CONSTRUCTION[a] KML-250MAH, KML-350MAF, KML-350MAH, KML-450MAF, KML-450MAHSpray TubesWater SupplyInletJunction BoxCondens
28[b] KML-250MWH, KML-350MWF, KML-350MWH, KML-450MWF, KML-450MWHSpray TubesWater SupplyInletJunction BoxControl BoxDrierHot Gas ValveCompressorWaterRe
29Spray TubesWater SupplyInletJunction BoxCondenserCondenserFan MotorControl BoxDrierHot Gas ValveCompressorFloat SwitchControl SwitchWater PumpExpans
3 • Please review this manual. It should be read carefully before the icemaker is servicedor maintenance operations performed. Only qualified servi
30[d] KML-600MWF, KML-600MWHSpray TubesJunction BoxWaterRegulatorControl BoxDrierHot Gas ValveFloat SwitchControl SwitchWater PumpExpansionValveCompre
31[e] KML-600MRF, KML-600MRHSpray TubesJunction BoxReceiverTankControl BoxDrierHot Gas ValveFloat SwitchControl SwitchWater PumpExpansionValveCompress
322. CONTROLLER BOARD[a] SOLID-STATE CONTROL1) A HOSHIZAKI exclusive solid-state control is employed in Modular Crescent Cubers.2) A Printed Circuit B
332) Defrost TimerThe defrost cycle starts when the Float Switch opens and completes the freeze cycle.But the Defrost Timer does not start counting un
34The green LED’s 1-4 represent the corresponding relays and energize and sequence 5seconds from initial start-up as follows:Sequence Step LED’s on L
35(Control Products HOS-001A Board)The application switch located between relay X3 & X4 must be set to match the originalboard application. Place
36[c] SEQUENCE1st Cycle1. Unit energized and Control Switch to “ICE” position. Water supply cycle starts.2. After 1 minute, Defrost cycle start
372nd Cycle and after with pump drainIMPORTANTFreeze cycle time is limited to 60 minutes evenif Float Switch does not open.1. Float Switch opens and s
38IMPORTANTFreeze cycle time is limited to 60 minutes evenif Float Switch does not open.2nd Cycle and after with no pump drain1. Float Switch opens an
39[d] CONTROLS AND ADJUSTMENTSThe Dip Switch is factory-adjusted to the following positions:FOR MODELS WITH THERMOSTAT:Switch Nos. 1 and 2:Used for ad
4III. TECHNICAL INFORMATION...471. WATER CIRCUI
401) Defrost ControlA thermistor (Semiconductor) is used for a defrost control sensor. The resistancevaries depending on the Suction Line temperature
413) Drain TimerThe Drain Timer is factory-adjusted, and no adjustment is required.SETTING TIMEDip Switch Dip SwitchNo. 3 No. 4 T1 T2OFF OFF 10 second
426) Bin ControlMODELS WITH THERMOSTATCAUTIONWhen the ambient temperature is below 45°F, the Bin Control Thermostatoperates to stop the icemaker even
43(iv) After Step (iii), de-energize the unit and confirm that the Defrost Timer is in theminimum position. Disconnect the resistor from the Controll
443. SWITCHESTwo control switches are used to control operation in the KML Series Modular CrescentCubers. These switches are referred to as the “Cont
454. MECHANICAL BIN CONTROL (THESE INSTRUCTIONS NOT APPLICABLE TO MODELS WITH THERMOSTAT)[a] PROXIMITY SWITCH1) This machine uses a lever-actuat
46[c] TROUBLESHOOTING (MECHANICAL BIN CONTROL ONLY)1) Machine will not start(i) Move dip switch No. 7 to the “OFF” position. If the machine starts
47III. TECHNICAL INFORMATION1. WATER CIRCUIT AND REFRIGERANT CIRCUIT[a] KML-250MAHKML-350MAF, KML-350MAHKML-450MAF, KML-450MAHKML-600MAF, KML-600MAH
48[b] KML-250MWHKML-350MWF, KML-350MWHKML-450MWF, KML-450MWHKML-600MWF, KML-600MWH
49[c] KML-600MRF, KML-600MRH
5[h] KML-450MAF ...72[i] KML-45
502. WIRING DIAGRAMS[a] KML-250MAH (Beginning Serial #L00001E, ending Serial #M10460F; KML-250MWH (Beginning Serial #L10001K, ending Seri
51Note: KML-250MAH Pressure SwitchCut-out 412.5 PSIGCut-in 327 ± 21.3 PSIG[b] KML-250MAH (Beginning Serial #M20461G); KML-250MW
52[c] KML-350MAF and KML-350MWFNote: KML-350MAF Pressure SwitchCut-out 412.5 PSIGCut-in 327 ± 21.3 PSIGKML-350MWF Pressure SwitchCut-out
53[d] KML-350MAH (Beginning Serial #L00001L, ending Serial #M10290F); KML-350MWH (Beginning Serial #L00001J, ending Serial #M30080F)Note: KML
54[e] KML-350MAH (Beginning Serial #M20291G); KML-350MWH (Beginning Serial #M40081G)Note: KML-350MAH Pressure SwitchCut-out 412.5
55Note: KML-450MAF Pressure SwitchCut-out 412.5 PSIGCut-in 327 ± 21.3 PSIG[f] KML-450MAF and KML-450MWFKML-450MWF Pressure SwitchCut-out
56[g] KML-450MAH (Beginning Serial #L00101C, ending Serial #L00950G); KML-450MWH (Beginning Serial #L00001D, ending Serial #L00200G)Note:
57[h] KML-450MAH (Beginning Serial #L20951H, ending Serial #M12770F); KML-450MWH (Beginning Serial #L10201H, ending Serial #M20710F)Note: KML
58[i] KML-450MAH (Beginning Serial #M22771G); KML-450MWH (Beginning Serial #M30711G)Note: KML-450MAH Pressure SwitchCut-out 412.5 PS
59+21.3- 0+21.3- 0Note: KML-600MWF Pressure SwitchCut-out 384 PSIGCut-in 284.5 ± 21.3 PSIGKML-600MAF, MRF Pressure SwitchCut-out 412.5
6I. SPECIFICATIONS1. KML-250MAH
60[k] KML-600MAH (Beginning Serial #L00001F, ending Serial #L00070F); KML-600MWH (Beginning Serial #L00001D, ending Serial #L00080E); K
61[l] KML-600MAH (Beginning Serial #L10071H, ending Serial #M10460G); KML-600MWH (Beginning Serial #L10081K, ending Serial #M10140E); KML-60
62[m] KML-600MAH (Beginning Serial #M2_ _ _ _ _); KML-600MWH (Beginning Serial #M20141F); KML-600MRH (Beginning Serial #M20331E)Note: KM
63**3. TIMING CHARTControlSw. inICEBinThermo-stat ONPressureSw. ONOverheatProtectReset Hi Temp Mid Temp Lo Temp Too Lo Temp Normal Too Hi Temp
64To Stand-by Cycle (When Control Sw. is turned OFF, Pressure Sw. is OFF, Thermistor Temp. exceedst1, or Bin Control is in full position)To Freeze Cyc
654. PERFORMANCE DATA [a] KML-250MAH
66[b] KML-250MWH
67 [c] KML-350MAF
68[d] KML-350MWF
69 [e] KML-350MAH
72. KML-250MWH
70[f] KML-350MWH (Serial #L00001J through M20060C)
71[g] KML-350MWH (Beginning Serial #M30061E)
72[h] KML-450MAF
73[i] KML-450MWF
74[j] KML-450MAH
75[k] KML-450MWH (Serial #L00001D through M10530B)
76[l] KML-450MWH (Beginning Serial #M20531D)
77[m] KML-600MAF
78[n] KML-600MWF
79[o] KML-600MRF
83. KML-350MAF
80Page KML-600MAH
81[q] KML-600MWH (Serial #L00001D through Serial #M10115C)
82[r] KML-600MWH (Beginning Serial #M10121E)
83[s] KML-600MRH
84 PROBLEM POSSIBLE CAUSE REMEDY[1] The icemaker a) Power Supply 1. “OFF” position. 1. Move to “ON” position will not start 2. Loose co
85 PROBLEM POSSIBLE CAUSE REMEDYl) Controller Board 1. Defective 1. See “II.2[e] CHECKING CONTROLLER BOARD.”[2] Water a) Float switch 1.
86 PROBLEM POSSIBLE CAUSE REMEDY[4] Water a) Water Solenoid 1. Diaphragm does not close. 1. Check for water leaks continues to Val
873. LOW ICE PRODUCTION PROBLEM POSSIBLE CAUSE REMEDY[1] Freeze cycle a) Float Switch 1. Leads short-circuit or 1. Check and replace.
88 PROBLEM POSSIBLE CAUSE REMEDY[1] Icemaker will a) Bin Control 1. Set too cold. 1. Adjust warmer. not stop when Thermostat 2. Def
89V. REMOVAL AND REPLACEMENT OF COMPONENTSIMPORTANTEnsure all components, fasteners and thumbscrews are securely in placeafter the equipment is servi
94. KML-350MWF
905) Disconnect the Vacuum Pump, and attach a Refrigerant Service Cylinder tothe High-side line. Remember to loosen the connection, and purge the airf
913. REMOVAL AND REPLACEMENT OF COMPRESSORIMPORTANTAlways install a new Drier every time the sealed refrigeration system is opened.Do not replace the
924. REMOVAL AND REPLACEMENT OF DRIERIMPORTANTAlways install a new Drier every time the sealed refrigeration system is opened.Do not replace the Drier
935. REMOVAL AND REPLACEMENT OF EXPANSION VALVEIMPORTANTSometimes moisture in the refrigerant circuit exceeds the Drier capacity andfreezes up at the
946. REMOVAL AND REPLACEMENT OF HOT GAS VALVE AND LINEVALVECAUTIONAlways use a copper tube of the same diameter and length when replacingthe hot gas l
9510) Cut the leads of the Solenoid allowing enough lead length to reconnect using closed end connectors.11) Connect the new Solenoid leads.12)
967. REMOVAL AND REPLACEMENT OF EVAPORATORIMPORTANTAlways install a new Drier every time the sealed refrigeration system isopened. Do not replace the
978. REMOVAL AND REPLACEMENT OF WATER REGULATING VALVE -WATER-COOLED MODEL ONLYIMPORTANTAlways install a new Drier every time the sealed refrigeration
989. ADJUSTMENT OF WATER REGULATING VALVE - WATER-COOLEDMODEL ONLYThe Water Regulating Valve (also called “WATER REGULATOR”) is factory-adjusted.No ad
9910. REMOVAL AND REPLACEMENT OF CONDENSING PRESSURE REGULATOR (C.P.R.) - REMOTE AIR-COOLED MODEL ONLYIMPORTANTAlways install a new Drier every t