Hoshizaki “A Superior Degree of Reliability” www.hoshizaki.com ModelsKM-1601MRH/3Modular Crescent CuberHoshizaki America, Inc. Issued: 7-22-2005Revise
10E. Electrical Connection WARNING1. Electrical connection must be hard-wired and must meet national, state, and local electrical code requirements. F
11•Usuallyanelectricalpermitandservicesofalicensedelectricianarerequired.•Themaximumallowablevoltagevariationis±10percentofthen
12F. Installation of Remote Condenser Unit WARNING1. Installation of the remote condenser unit must be performed by properly trained and EPA-certied
133. Setup1) Secure the legs to the remote condenser unit with the 8 bolts and nuts provided. See Fig. 7.2) The legs have 8 mounting holes. Secure the
14d. Tighten the connection with a wrench until it is tight. At this point, the nut has covered most of the threads on the male tting. e. Mark a refe
156) Evacuate through the Schrader access ports on the Parker quick connect couplings and charge with R-404A refrigerant vapor to a pressure of 15 to
165. Refrigerant Charge (Line Set Exceeding 66 Feet)CAUTIONThe icemaker, line set, and remote condenser unit must contain the same type of refrigerant
177. Stacking Remote Condenser Units1) Install the lower remote condenser unit as described earlier in this section.2) Place the upper remote condense
18G. Water Supply and Drain Connections See Fig. 13 WARNING1. Water supply and drain connections must be installed in accordance with applicable na
19Fig. 13KM-1601MRH/31. Icemaker•Icemakerwatersupplyinletis1/2"femalepipethread(FPT).Aminimumof3/8"nominal ID copper water tu
2IMPORTANTOnly qualied service technicians should install, service, and maintain the icemaker. No installation, service, or maintenance should be und
20H. Final Checklist WARNINGCHOKING HAZARD: Ensure all components, fasteners, and thumbscrews aresecurely in place after installation. Make sure that
21I. Startup WARNING1. All parts are factory-adjusted. Improper adjustments may adversely affect safety, performance, component life, and warranty cov
22III. Cleaning and Maintenance InstructionsIMPORTANTEnsure all components, fasteners and thumbscrews are securely in place after any maintenance or c
231. Cleaning Procedure1)Dilute27.oz.(798ml)ofHoshizaki"ScaleAway"with5gal.(19l)ofwarmwater.2) Remove all ice from the ev
2426)Removetherubbercapcoveringtheoverowpipeinthewatertank.Removetheoverowpipebyturningitcounterclockwise.Drainthewatertank.
25B. Maintenance InstructionsIMPORTANTThis icemaker must be maintained individually, referring to the instruction manual and labels provided with the
262. Drain the water tank:1) Turn off the power supply, then remove the front panel. Move the control switch to the "OFF"position.2) Remove
27HOSHIZAKI AMERICA, INC.618 Hwy. 74 S., Peachtree City, GA 30269 USA TEL (770) 487-2331 FAX (770) 487-3360 www.hoshizaki.com 1A2913-010
3IMPORTANTThis manual should be read carefully before the icemaker is installed and operated. Only qualied service technicians should install, servic
4Important Safety InformationThroughout this manual, notices appear to bring your attention to situations which could result in death, serious injury,
5I. SpecicationsA. Nameplate Rating1. KM-1601MRH (remote air-cooled) HOSHIZAKI ICE MAKER See the nameplate for electrical and refrigeration specicat
6 HOSHIZAKI ICE MAKER 2. KM-1601MRH3 (remote air-cooled)See the nameplate for electrical and refrigeration specications. This nameplate is located on
7B. Dimensions/ConnectionsUnit: mm [in.]
8II. Installation and Operating Instructions WARNING1. This icemaker must be installed in accordance with applicable national, state, and local codes
9C. LocationCAUTION1. This icemaker is not intended for outdoor use. Normal operating ambient temperature should be within 45°F to 100°F (7°C to 38°C)